Discharge- and groundingsticks

Is toegevoegd aan uw winkelmandje

Ga naar winkelmandje

Discharge- and groundingsticks

Dit product is niet online te bestellen. Neem contact met ons op voor advies en bestelmogelijkheden.

Product description

Discharge and grounding sticks are a vital part of high voltage safety practices.
The sticks have been specifically designed for high voltage testing in the field or laboratory.
Depending on the application, only the ground stick may be used or a discharge and ground stick may have to be used.

AC sources

AC high voltage sources such as high voltage transformers and resonant test systems are typically grounded with ground sticks appropriate for their physical size and output voltage.
Phenix Technologies’ ground sticks are ideally suited for this use.
The generous length and the hand guard insure that the operator is distant when the high voltage output is grounded.
All ground sticks are equipped with a hook that attaches to the high voltage electrode of the source.
The ground cable is equipped with an alligator clamp for connection to earth ground.

DC sources

When testing with DC, extra caution has to be taken in order to dissipate the stored energy in capacitive test objects such as cables, motors and transformers.
These test objects have the capability to store large amounts of energy long after the high voltage is turned off.
High Voltage DC sources require two different sticks.
The first stick typically used is called a discharge stick.
The discharge stick removes the stored energy through a resistor connected to ground.
In this way the discharge happens over time and not instantaneously and potentially dangerously as with a direct short (ground stick).
In addition, this limits transients and or traveling waves that could damage objects under test.
First, the stored energy is minimized; typically by watching the output voltmeter return close to zero.
Next, the ground stick is applied to remove any remaining charge and directly connect the high voltage source at test object to ground.
Discharge sticks are not considered as grounding devices due to the resistance in the circuit.
It should be noted that discharge sticks have three ratings that need to be considered for safe operation: the instantaneous energy (kilo joule) rating, continuous operating wattage of the discharge resistor, and the maxi- mum discharge voltage rating.
The Model DS100-2 is equipped with a hook that attaches to the high voltage electrode of the source.
The ground cable is equipped with an alligator clamp for connection to earth ground.

Design features

• Generous length is an additional safety factor
• Two piece design allows easy storage and transportation
• Safety hand guard on all sticks
• High discharge capability (Model DS100-2)
• Combination ground and discharge stick (Model GSDS-30)
Note that the following information is for reference only and that there are operating guides for national and international safety standards that specify detailed safety requirements. It is the user’s responsibility to verify that Phenix Technologies’ products are applicable to these standards.
Any high voltage source that does not have a visible ground wire or ground device attached (high voltage output shorted to ground) are generally considered live and dangerous.
It is established practice never to touch or come close to the high voltage source when the source is not grounded.
Ground Sticks are one of the accepted methods to apply a temporary ground to these sources.
For permanent grounds bolted ground- ing cables are typically used.”

Groundstick specifications

ModelGS30GS100-2GS160-2
AC Rated voltage30 kVAC100 kVAC100 kVAC
DC Rated voltage30 kVDC100 kVDC160 kVDC
Cable length7 m7 m7 m
Assembled length1041 mm889 mm1168 mm
Weight1,4 kg1.8 kg2.2 kg

Dischargestick specifications

ModelDS 100-2
DC Rated voltage100 kVDC
Maximum instantaneous energy absorbtion40kJ
Resistance100 kOHM
Maximum discharge capacitance at rated voltage8.6 µF @ 100 kVDC
Maximum steady state power dissipation100 w
Cable length7 m
Length1955 mm
Weight2.2 kg

Dischargestick Calculations

Combination Ground-/Dischargestick specifications

ModelGSDS-30
AC/DC Ground rating30 kV
DC Discharge rating30 KVDC
Maximum instantaneous energy absorption10.8 kJ
Resistance25 kOHM
Maximum discharge capacitance at rated voltage24 μF @ 30 kVDC
Maximum steady state power dissipation30 W
Cablelength7 m
Length991 mm
Weight1.4 kg

Werkelijke specificaties kunnen afwijken van de op deze website vermelde specificaties. Aan de op deze website vermelde specificaties kunnen geen rechten worden ontleend.